40.5 kV Embedded Pole — 1250 / 1600 A
An embedded pole for vacuum circuit breaker assembly, with conductor construction, mounting datums and drive interfaces matched to the selected configuration.
Technical Description
This embedded pole is intended for a matched vacuum circuit breaker assembly. Select the current configuration using its conductor construction and drawing reference. Check terminal connections, mounting datums, phase arrangement and the operating mechanism before selection. A current option does not establish that the same physical pole serves both configurations. Define the supplied pole assembly and accessories, with insulation, partial discharge and interruption data tied to the selected version.
Technical specifications
| Parameter | Value / conditions |
|---|---|
| Rated voltage | 40.5 kV |
| Rated current | 1250 / 1600 ACurrent options require the corresponding conductor configuration. |
| Rated frequency | 50/60 Hz |
| Rated peak withstand current | 80 kA |
| Rated short-time withstand current (4 s) | 31.5 kA |
| Power-frequency withstand voltage (1 min) | 95 kV |
| Lightning impulse withstand voltage (peak) | 185 kV |
| Circuit resistance at rated contact force | ≤20 μΩ |
| Contact erosion limit | 3 mm |
Values apply to the listed configuration. Use the matching drawing when specifying interfaces.